MCA is 27 and the Breaker is a 50A - Short #219

19 Nov 2024 • 6 min • EN
6 min
00:00
06:11
No file found

In this short podcast episode, Bryan and Mike from DITEK talk about what to do in tricky electrical scenarios, such as when the MCA is 27 and you have a 50A breaker. When you size an HVAC system for compatibility with voltage monitors, like the DITEK Kool Guard, you need to pay attention to the MCA (minimum circuit ampacity), which should not be confused with MOCP (maximum overcurrent protection or breaker size). As long as the MCA is 40 amps or lower, you can attach the HVAC condenser to the Kool Guard. The KG2 also accepts wire sizes up to 6 AWG. The Kool Guard is NOT a source of overcurrent protection; it is a voltage monitor rated for carrying current, which means ratings will be in MCA, not MOCP. MOCP is designed to deal with high starting amps and lets users know the maximum allowable current for a circuit so that it can trip properly when that current is exceeded. According to Section 440 of the National Electrical Code (NEC), motors with internal overload protection allow for a difference between the MCA and MOCP. You may find higher MOCPs on inverter-driven systems.   Learn more about DITEK at https://www.diteksurgeprotection.com/.  Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.  Purchase your tickets or learn more about the 6th Annual HVACR Training Symposium at https://hvacrschool.com/symposium. Subscribe to our podcast on your iPhone or Android.   Subscribe to our YouTube channel.  Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.

From "HVAC School - For Techs, By Techs"

Listen on your iPhone

Download our iOS app and listen to interviews anywhere. Enjoy all of the listener functions in one slick package. Why not give it a try?

App Store Logo
application screenshot

Popular categories